Cookie Consent by Free Privacy Policy website Skip to content

Weight Transmitters with direct connection of one ore more load cells and a wide range of outputs for an easy integration in every industrial and automation system. Comfortable and immediate installation on DIN bar and/or OMEGA bar.

Digital / Analog load cell amplifier

Click on the image to enlarge

Transmitter RQA Transmitter RQA Drawing

Technical specifications

Power supply24 V direct current ± 10 % protected against inversion of polarity. Protection with resettable fuse
Max power consumption1 W
IsolationClass II
Installation CategoryCategory II
Operating temperature-10 / +50 °C (14 / 122 °F) Humidity Maximum 85% non-condensing
Storage temperature-20 / +60°C (-4 / +140°F)
Led2 LED with 3 mm (function status)
Keyboard3 keys (behind red front cover)
Overall dimensions110 mm x 120 mm x 23 mm (l x h x p) including terminals
MountingSupport DIN or OMEGA rail
Case materialBlend ABS/PC self-extinguishing
ConnectionsRemovable screw terminals. Pitch screws terminal blocks 5.08 mm
Load cell input featuresMaximum 4 load cells with 350 Ω in parallel (or 8 cells with 700 Ω)
Power supply load cells4V
Linearity< 0.01% of full scale
Temperature deviation< 0.001% of full scale/C°
Internal resolution16 - 24 bit
Measuring range-2.6 mV/V - +2.6 mV/V
Digital filter0.1 Hz - 50 Hz
Number of weight decimalsfrom 0 to 3 decimal digit
Zero / FS CalibrationExecutable through buttons
Cell cable interruption checkAlways present
Analog output in tension± 10 V / ± 5 V
Resolution16 bits
CalibrationBy push-buttons
Impedance≥ 10 kΩ
Linearity0,03 % of full scale
Temperature deviation< 0,002 % of full scale/°C
Analog output under current0 – 20 A / 4 – 20 mA
Resolution16 bits
CalibrationDigital through buttons
Impedance≤ 300 Ω
Linearity0,03 % of full scale
Temperature deviation< 0,002 % of full scale/°C
Conforms to standardsCompliance to EMC norms: EN61000-6-2, EN61000-6-3, Compliance electric safety: EN 61010-1

For complete and up-to-date technical specifications please refer to the datasheet you can download here

Download PDF datasheet

Connections

Type6 pins Terminal 5.08 mm pitch
LengthND
11Power supply 24 Vdc
12Power supply GND
13Shield
14Analog outputs shield
15Analog output 4-20 / 0-20 mA
16Analog output ± 10V ± 5V
Type7 pins Terminal 5.08 mm pitch 6 wires load cell options
LengthND
1Shield
2- Excitation
3+ Excitation
4+ Reference
5- Reference
6- Signal
7+ Signal
Type7 pins Terminal 5.08 mm pitch 4 wires load cells options
LengthND
1Shield
2- Excitation Connect to terminal n. 5
3+ Excitation Connect to terminal n. 4
6- Signal
7+ Signal
Connections Transmitter RQA

Load cell mounting

General guidelines for installing and mounting load cells:

  • Respect the direction in which forces are applied to the load cells
  • Do not exceed the temperature limits shown on the rating plate
  • Do not remove the labels from the cells
  • Protect cables properly with sheaths or cable ducts
  • Connect each cell to earth with a suitable cable, bridging the plates of the mounting accessories if necessary
  • Do not weld on the mechanical structure once the cells are in place
  • Avoid or minimise mechanical constraints between the fixed structure and the weighed structure, to prevent weighing errors and zero return problems
  • When vibrations or dynamic loads are present, protect the cells with anti-vibration mounts
  • Protect the cells from dust build-up with suitable covers