GICAM sells various types of signal converter. We have signal converters that transmit serial protocols by radio frequencies, very simple to program and control. Our converters are suitable for use in industry. We offer signal converters that transform analog input signals into standardized analog signals, and signal converters that can be connected to devices that have RS-485 or RS-422 protocols.

4 – 20 mA CONVERTER

Click on the image to enlarge

Converter SG02

Technical specifications

Board power supply12-30 V dc
Cell power supply4 V dc per cell (1 cell of 350 Ω or 700 Ω) protected against short circuit
Power assumption0.6W with 350 Ohm cell
Output4 mA ÷ 20 mA (load <=250W)
Input sensitivity1 – 2 mV / V depending on resistance R3 (15 ppm): 1mV/V with R3 = 200 Ω, 2 mV / V without R3
Dimensions35 x 22 x 8 mm
ConnectionsWires to be welded
Cell connectionWith 4 wires
Storage temperature- 10 °C / + 50 °C (14 °F / 122 °F)
Operating temperature- 20 °C / + 60 °C (- 4 °F / 140 °F)
Linearity0.02%
Thermal stability30 ppm/°C
Zero adjustment± 10% full scale through multi-turn trimmer
Gain adjustment±10% of full scale using multi-turn trimmer
Analog Filter50 Hz
Protection from incorrect connectionsReverse polarity protection of the power supply, short-circuit protection on the mA signal

For complete and up-to-date technical specifications please refer to the datasheet you can download here

Download PDF datasheet

Connections

TypeSG02 Connection
LengthND
1+ Exc. Load cell
2+ Signal load cell
3- Signal load cell
4- Exc. Load cell
5+ Power Supply 12 - 30 Vcc
6- Power Supply
7Output 4 - 20 mA (the output GND is power pin 6)
Connections Converter SG02

Load cell mounting

General guidelines for installing and mounting load cells:

  • Respect the direction in which forces are applied to the load cells
  • Do not exceed the temperature limits shown on the rating plate
  • Do not remove the labels from the cells
  • Protect cables properly with sheaths or cable ducts
  • Connect each cell to earth with a suitable cable, bridging the plates of the mounting accessories if necessary
  • Do not weld on the mechanical structure once the cells are in place
  • Avoid or minimise mechanical constraints between the fixed structure and the weighed structure, to prevent weighing errors and zero return problems
  • When vibrations or dynamic loads are present, protect the cells with anti-vibration mounts
  • Protect the cells from dust build-up with suitable covers